Temperature Controller1/16DIN - 48 x 48 M3 lineccUser manual • M.I.U.M3 -4/03.01 • Cod. J30-478-1AM3 IEASCON spa20021 Bollate(Milano) Italyvia Falzare
92 - Electrical connectionsPRECAUTIONSBDespite the fact that the instrumenthas been designed to work in anharsh and noisy environmental(level IV of th
102 - Electrical connections2.3 EXAMPLE OF WIRING DIAGRAM (HEAT COOL CONTROL) BFuse[5]6SupervisionPower supplyRS4854…20mACT Current transformer 50 m
112 - Electrical connections2.3.1 POWER SUPPLY BSwitching power supply with mul-tiple isolation and internal PTC• Standard version:nominal voltage:10
122 - Electrical connectionsD For mA, mVRj >10MΩD1 With 2 wires transducerD2 With 3 wires transducer[1] Auxiliary power supply for externaltransmit
132 - Electrical connections2.3.4 OP1 - OP2 - OP3 OUTPUTSBAlarmsAL2OP1HeatOP2-R OP3OP2-LHeatOP1 OP3OP1HeatOP3CoolOP2-R[1]OP1HeatOP2-LCoolOP3[1]OP2-LH
HeatloadStaticrelay1011OP2142 - Electrical connectionsRelay output• SPST Relay N.O., 2A/250 V~for resistive load, fuse 2A~ TTriac output• N.O. contact
152 - Electrical connections2.3.6 OP4 OUTPUT (option)B2.3.7 SERIAL COMMUNICATIONS (option)BPV or SP retransmission• Galvanic isolation500V~/1 min•
163 - Product coding3 PRODUCT CODINGThe complete code is shown onthe instrument label. The informa-tions about product coding areaccessible from the f
173 - Product codingSerial Communications DOptionsNot fitted0None3Current transformer input (CT)RS485Modbus/Jbus protocol0None6Transmitter Power Suppl
183 - Product coding3.2 CONFIGURATION CODINGThe configuration code consists of4 digits that identify the operat-ing characteristic of the controller,
Temperature Controller1/16DIN - 48 x 48 M3 linecc274.8275.01233RUNULCUSLISTED
193 - Product codingAIf, when the controller is poweredup for the first time, the displayshows the following messageit means that the controller hasno
204 - Operations4 OPERATIONS4.1.A KEYS FUNCTIONS AND DISPLAY IN OPERATOR MODE274.8275.0123MANSetpointsettingOP1 output ONOP2 output ONOP3 output ONMe
214 - Operations4.2 DISPLAY During the operation, the para-meters values cannot be modi-fied by the user4.2.1 OF THEPROCESS VARIABLES4.2.2 OF THE CON
224 - OperationsOperatormode working SetpointdisplayedLocal Setpoint displaySetpoint modificationSetpoint entry.The operation isacknowledged byone fla
Unit °CUnit °fUnit °CUnit °fUnitnoneUnit ph234 - OperationsEngineering UnitsDegree CentigradeDegree FahrenheitDegree CentigradeDegree Fahrenheitn
244 - Operations4.3.3 KEYPAD LOCKTo lock/unlock the keypad pressthe keys í and è simulta-neously for 2 seconds.To confirm the keypad lock/unlockthe d
275..0é 5:0t.i.é 5:0p.b.é 0A3s.p274.8t.runO.C.t.c.é 1:00t.d.é 20é 1:00254 - Operations4.4 PARAMETERISATIONAThe parameter setting procedurehas a
tune5000é 0:5d.bndé100:0Op. Hé100:0Op.HChy.é 0:5hy. Cr.C.Gaé 20t.c. Cé 33pAssé 0A2s.pOKé 1:0éF.sécalaé 1é 0é Offé OfféIn.sécalatiMes.p. 2sl
é 1é 0é 1éIn.sécalaéF.sécalapassst.tMsa.OpAddrrt.loénoneé Offé Offé Offé OffA3L.bt.LbAt.FilIn.shé 1é100:0é 0:5énones.p.s.Ut.h.s.UOp.HsA2hyst.
284 - Operations4.5 PARAMETERSThe controller parameters havebeen organised in group, accord-ing to their functionality area.AL2 alarm threshold AL3 al
2InformationccNOTESON ELECTRICSAFETY ANDELECTROMAGNETICCOMPATIBILITY.Please, read carefully these instructions before proceeding withthe installation
294 - OperationsProportional bandThis parameter specifies the pro-portional band coefficient that mul-tiplies the error (SP - PV)Integral time It is t
304 - OperationsSetpoint ramp upSetpointramp downThis parameter specifies the max-imum rate of change of the Setpointin digit/min. When the parameter
314 - OperationsInput filter time constantTime constant, in seconds, of the RCinput filter applied to the PV input.When this parameter is set to Offth
By a sole PID control algorithm, thecontroller handles two different out-puts, one of these performs theHeat action, the other one the Coolaction.It i
334 - OperationsOP4 output, if present, retransmitslinearised PV or the SP.On configuration (see page 37) itis possible to set: Output range0=20 / 4=
344 - OperationsCURRENT TRANSFORMER INPUTExample:• T/C S, range 0…1600°C• Output range, 4…20 mA• Retransmitted signal PV on800…1200°C rangeWith rt.lo
275..0274.8protbaudHt.f.sCodertHretrt.run354 - Operations4.6 CONFIGURATIONThe configuration of the controlleris specified through a 4 digit codethat
2002tuneI L M NA2s.pCon2sc.losc.Hisc.d.dConft.ActUnitt.Mod5000pAssOKHigh range [2](linear scale only)-999…9999Timer/Start-up operating mode (if optio
pass 33OK374 - OperationsCode entryfrom 0 to 4999 (33 default from factory)The entered password must correspond tothe one store in the Code parameter
385 - Automatic tune5 AUTOMATICTUNEStart/stop of the Fuzzy TuningThe Tuning operation can bestarted or stopped any time.The green led { blinking goes
3Table of contents1 INSTALLATION...
396 - Special functions6 SPECIAL FUNCTIONSTwo special functions are available:6.1 Start-up6.2 TimerIn order to have the above func-tions the product c
406 - Special functionsThere are two possibilities:A Start-up Setpoint #sp.sUlower than the local Setpoint.The “Hold” phase starts whenthe process v
416 - Special functionsTo use AL3 in addition to this func-tion, set the parameter #Con2(AL3 configuration code) to # 0..AThe Timer can’t be enable
426 - Special functions6.2.2 TIMER STARTINGDepending on the Timer action#t.act selection, there can be twodifferent starting ways:- Automatic at the p
436 - Special functions6.2.4 TIMER COUNTING MODESA Counting start time inside the band, end in control mode.The time counting starts only when the er
447 - Technical specification7 TECHNICAL SPECIFICATIONSCommon characteristicsA/D converter with resolution of 50.000 pointsUpdate measurement time: 0.
457 - Technical specificationFeatures(at 25°C environmental temp.)Operating mode and OutputsControl modeOP1 outputOP2 outputOP3 outputCT auxiliary inp
467 - Technical specificationActionActive highActive lowAction typeDeviation threshold ±rangeBand threshold 0…rangeAbsolute threshold whole rangeSpec
477- Technical specificationGeneral characteristicsElectromagnetic compatibilityProtection EN60529 (IEC 529)Compliance to the CE standards (see page 2
1 WARRANTYWe warrant that the prod-ucts will be free fromdefects in material andworkmanship for 3 yearsfrom the date of delivery.The warranty above s
41 - Installation1 INSTALLATIONInstallation must only be carriedout by qualified personnel.Before proceeding with the instal-lation of this controller
SUBSIDIARYFRANCEASCON FRANCEPhone 0033 1 64 30 62 62Fax 0033 1 64 30 84 98AGENCE SUD-ESTPhone 0033 4 74 27 82 81Fax 0033 4 74 27 81 71AGENCE RÉGION-ES
51 - Installation1.2 DIMENSIONAL DETAILS48 mm1.89 in120 mm4.72 in48 mm1.89 in20 mm max0.79 in max1.3 PANEL CUT-OUT65 mm min2.56 in min45+0.6 mm1.7
61 - InstallationSpecial conditionsMAltitude > 2000 mTTemperature >50°C%RhHumidity > 95 %PConducting atmosphereUse filterWarm upUse forced ai
71 - Installation1.5.1 INSERT THE INSTRUMENT1 Prepare panel cut-out2 Check front panel gasket posi-tion3 Insert the instrument through the cut-outUL
82 - Electrical connections2 ELECTRICALCONNECTIONSUL note[1] Use 60/70 °C copper (Cu) con-ductor only.2.1 TERMINATION UNIT [1]B18 screw terminalsOpti